APPLICATION STORY
Chemical Transfer
Flow measurement and control strategy developed for offloading and transferring 2-EH and DINP chemicals.
On this page
Overview
A chemical production site required four flow measurement points for offloading and transferring 2-EH and DINP from new bulk storage tanks.
The challenge
Each duty had different accuracy, control and media requirements, so one measurement technology was not automatically suitable for every line.
- Provide two offloading and two transfer measurements.
- Integrate all measurement points with the PLC.
- Control 2-EH feed rate to manage exothermic reaction risk.
- Measure non-conductive DINP without using a magnetic flowmeter.
Our solution
Quality Lab Solutions compared turbine and Coriolis technologies against the process, control and commercial requirements of each line.
- Considered turbine measurement for less critical offloading duties.
- Recommended Coriolis measurement for controlled 2-EH transfer.
- Included downstream flow-control valve integration.
- Rejected magnetic flow measurement for non-conductive DINP.
Results
The proposed architecture covered four measurement points and allowed operators to set controlled transfer rates, including a 20 l/min operating example for the 2-EH feed line.
Customer benefits
The customer received a duty-by-duty solution instead of an unnecessarily uniform specification.
- Improved control of chemical feed rate.
- Reduced risk of temperature rise during vessel charging.
- Appropriate technology for non-conductive media.
- PLC-ready measurement and control signals.
Products used


Download resources
Need help with your application?
Our engineers can help you find the right instrumentation for your process.
Speak to Engineering →